/00379884JUMO IGBT Power Converter70A with amplitude controlB 70.9050.0Operating Manual02.08
2 Introduction10 [IGBT Power Converter 70A] 02.082.4 Brief descriptionInstrument The J IPC is a IGBT power converter for controlling heater loads tha
02.08 [IGBT Power Converter 70A] 113 Installation3.1 Important notes on installationSafety regulationsk The choice of cable, the installation and the
3 Installation12 [IGBT Power Converter 70A] 02.08The earth leakage current of the IPC power converter with a filter wired into thesupply lead is less
02.08 [IGBT Power Converter 70A] 133 InstallationPositioning of the chokeh The choke should be installed close to the converter.Connection h Check the
3 Installation14 [IGBT Power Converter 70A] 02.08HUnder no circumstances may the voltage supply to the controlsection be switched on before the load v
02.08 [IGBT Power Converter 70A] 153 Installation3.2 Filtering and interference suppressionSystem Compliance with the EMC standards can only be achiev
3 Installation16 [IGBT Power Converter 70A] 02.08EVC compliant designThe user/owner is responsible for the specific application complying with theEMC
02.08 [IGBT Power Converter 70A] 173 Installation3.3 Ambient conditionsMisuse The instrument is not suitable for use in areas with an explosion hazard
3 Installation18 [IGBT Power Converter 70A] 02.08The power loss (W) is obtained by multiplying this power loss factor by theload current (e.g. 65A) th
02.08 [IGBT Power Converter 70A] 193 InstallationDimensions Type 709050/X1-XX-XXX-XXX-070/XXX 3.4 Spacingsh Allow a clearance of 10 cm from the floor.
3 Installation20 [IGBT Power Converter 70A] 02.083.4.1 Opening the housingh Disconnect the built-in converter from the voltage supply on all polesh Un
02.08 [IGBT Power Converter 70A] 214 Electrical connection4.1 Screw connections in the power sectionTool - Screwdriver- Open jaw spanner, width across
4 Electrical connection22 [IGBT Power Converter 70A] 02.08Phase / N The diagram shows the wiring for single-phase operation Phase / N fortype 709050/
02.08 [IGBT Power Converter 70A] 234 Electrical connection4.1.1 Suitable cables and cross-sectionsPE conductor The cross-section of the PE conductor m
4 Electrical connection24 [IGBT Power Converter 70A] 02.084.1.2 Electrical isolationThe control section, including the inputs and outputs, as well as
02.08 [IGBT Power Converter 70A] 254 Electrical connection4.1.4 Wiring of the screw terminalsPosition The following diagram shows the position of the
4 Electrical connection26 [IGBT Power Converter 70A] 02.08Choke connection 1CCLoad connection 1D +D -Connection for terminal screw X102 DetailCurren
02.08 [IGBT Power Converter 70A] 275 Settings5.1 Operating principleThe J IPC can be used wherever a transformer was previously used toreduce the vol
5 Settings28 [IGBT Power Converter 70A] 02.085.2 Setting switches and jumpersSwitch positionSwitch number S1011 2 3 4 5 6 7 8 9 10 11 S103 S104 S105 X
02.08 [IGBT Power Converter 70A] 295 Settings5.3 Subordinate control loopSubordinate control lops are primarily used to eliminate or compensate forext
02.08 [IGBT Power Converter 70A] 31 Contents1 Contents ... 32
5 Settings30 [IGBT Power Converter 70A] 02.085.5 Control inputsThe internal switches S8, S9 and S104 are used to adapt the converter to theavailable c
02.08 [IGBT Power Converter 70A] 315 Settings5.5.1 Combination of external potentiometer and electronic controllerController with current outputThe vo
5 Settings32 [IGBT Power Converter 70A] 02.085.6 Firing pulse inhibitThe firing pulse inhibit function provides a simple way of switchingto high power
02.08 [IGBT Power Converter 70A] 335 Settings5.9 Control input adjustment (max. Power adjust)The „max. Power adjust“ trimmer at the front can be used
5 Settings34 [IGBT Power Converter 70A] 02.085.11 Setting the current limit (max. current adjust)h The front „max. current adjust“ trimmer can be used
02.08 [IGBT Power Converter 70A] 355 SettingsType: relayType: optocouplerIn the case of a load fault, the floating contact drops out, or the collector
5 Settings36 [IGBT Power Converter 70A] 02.08Alternativesetting option:To simulate a load fail, adjust the „load fail adjust“ trimmer such that the ye
02.08 [IGBT Power Converter 70A] 375 Settings5.13 Adjusting the output level signal (output adjust U2, P , I2 )In the factory settings, the output lev
5 Settings38 [IGBT Power Converter 70A] 02.08
02.08 [IGBT Power Converter 70A] 396 Technical data6.1 Voltage supply6.2 Control6.3 Fault signal output6.4 General characteristicsVoltage supply Power
4 [IGBT Power Converter 70A] 02.085.8 Trimmer settings ...
6 Technical data40 [IGBT Power Converter 70A] 02.08Power loss Ptot (W) Power loss occurs in the form of thermal discharge at the cooling body of the p
02.08 [IGBT Power Converter 70A] 416 Technical data6.5 Choke data6.6 EMC filterType: Dimensions Connectioncross sectionConnection, Tightening torqueWe
6 Technical data42 [IGBT Power Converter 70A] 02.08
02.08 [IGBT Power Converter 70A] 437 TroubleshootingWhat is happening? Cause / Remedy InformationGreen power LED doesnot light up- Voltage supply to c
44 [IGBT Power Converter 70A] 02.087 TroubleshootingIPC is producing power,although no setpointvalue is set- Check switches S 101/ 8 and 9 for control
02.08 [IGBT Power Converter 70A] 457 Troubleshooting
JUMO GmbH & Co. KG JUMO Instrument Co. Ltd. JUMO Process Control, Inc.Street address:Moritz-Juchheim-Straße 136039 Fulda, GermanyDelivery address:
02.08 [IGBT Power Converter 70A] 52 Introduction2.1 PrefaceService hotline For technical questionsPhone support in Germany:Phone: +49 (0)661 6003-300
2 Introduction6 [IGBT Power Converter 70A] 02.082.2 Typographical conventions2.2.1 Warning signsDangerCaution:ESD2.2.2 Note signsNoteReferenceFootnote
02.08 [IGBT Power Converter 70A] 72 Introduction2.2.3 Performing an actionActioninstructionVital texth Plug in the connectorThis symbol indicates that
2 Introduction8 [IGBT Power Converter 70A] 02.082.3 Order detailsThe nameplate is glued onto the right panel of the housing. 2.3.1 Standard accessorie
02.08 [IGBT Power Converter 70A] 92 Introduction2.3.2 AccessoriesChoke: L=0.6mH/IN= 75A, protection rating IP 10, as per EN 60 529EMC filterDimensions