Jumo 705021 mTRON T - Analog Input Module, 8-Ch. Operat User Manual

Browse online or download User Manual for Equipment Jumo 705021 mTRON T - Analog Input Module, 8-Ch. Operat. JUMO 705021 mTRON T - Analog Input Module, 8-Ch. Operating Manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
JUMO mTRON T
Measuring, Control, and Automation System
Analog Input Module 8-Channel
B 705021.0
Operating Manual
2013-06-18/00575627
Page view 0
1 2 3 4 5 6 ... 55 56

Summary of Contents

Page 1 - JUMO mTRON T

JUMO mTRON TMeasuring, Control, and Automation SystemAnalog Input Module 8-ChannelB 705021.0Operating Manual2013-06-18/00575627

Page 2

1 Introduction101.3.4 DisposalDisposing of the deviceDisposing of the packaging materialThe entire packaging material (cardboard packaging, inserts, p

Page 3 - Contents

111 Introduction1.4 Identifying the Device Version1.4.1 NameplatesPositionThe nameplate (B) is affixed to the module case.An additional nameplate with

Page 4

1 Introduction12Fabrication no. (F-Nr)Among other things, the fabrication number contains the date of production (year/week).Example: F-Nr = 007003380

Page 5

132 Description2.1 Brief descriptionThe analog input module 8-channel is equipped with eight analog inputs for RTD temperature probes in 2-wire circui

Page 6

2 Description14

Page 7

153 Installation3.1 General information on installation/dismountingMounting siteAll modules have protection type IP20 and are only intended for use in

Page 8

3 Installation16Minimum distances3.2 Installation/dismounting on DIN railAll modules in the system are intended for installation on a DIN rail accordi

Page 9

173 InstallationInstallation, using the example of a multichannel controller module 705010Example installationProcedure:(A) (A1)(A2)Step Activity1 Mou

Page 10 - 1 Introduction

3 Installation18Dismounting, using the example of a multichannel controller module 705010Removing the multichannel controller module from the DIN rail

Page 11

193 Installation3 Move the modules (B) on the right next to the multichannel controller module that is to be replaced (A) a minimum of 20 mm to the ri

Page 13 - 2 Description

3 Installation203.3 Replacing module inserts3.3.1 Input/output modulesReplacement of a module insert, using the example of a multichannel controller m

Page 14

213 InstallationRemoving the module insertMounting the module insertCAUTION!Only module inserts of the same type may be used for the replacement.Other

Page 15 - 3 Installation

3 Installation223.4 Dimensions103.622.56.610194.5101.514.5

Page 16

234 Electrical connection4.1 Installation notesQualification of personnel• Work on the modules must only be carried out to the extent described and, l

Page 17

4 Electrical connection24References to other information• The electromagnetic compatibility meets the standards and regulations cited in the techni-ca

Page 18

254 Electrical connection4.3 Connection diagram4.3.1 Display and connection elementsCAUTION!At maximum load, the temperature may exceed 60 °C at the t

Page 19

4 Electrical connection264.3.2 Analog inputs4.3.3 Digital input4.4 Functional testThe voltage supply must be tested on completion of the electrical co

Page 20

275 Operation5.1 Display and connection elements(1) Status displays (LED)P = Voltage supplyS = Status1 = Digital input(LED is lit: Active)(2) Analog i

Page 21

5 Operation285.2 LED displays"P" LED (Power)The LED is permanently lit in green if the module is being supplied with voltage."S" L

Page 22

295 Operation5.2.2 System states and errorsThe following table lists all the system states and errors that are indicated by the "S" LED (Sta

Page 23 - 4 Electrical connection

3Contents1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51.1 Available tec

Page 24

5 Operation30

Page 25

316 Configuration6.1 Digital selectorThe digital selector contains all digital signals that are available in the analog input module 8-channel to conf

Page 26

6 Configuration326.2 Analog inputsThe eight analog inputs are measuring inputs for RTD temperature probes in 2-wire circuit.Setup dialogParameterParam

Page 27 - 5 Operation

336 ConfigurationOffset typeTo offset plant-specific deviations, the measured value can be offset for each analog input. When doing this, the offset t

Page 28

6 Configuration346.2.1 AlarmsLimit value monitoring with one or two alarms and various alarm types can be activated for each analog input. In addition

Page 29

356 ConfigurationAlarm type and switching differentialEvent textSetup program: Selection of text from a listClick the "..." button to open a

Page 30

6 Configuration366.2.2 Fine adjustmentYou can use customer-specific fine adjustment to correct the measured values of the analog input. In contrast to

Page 31 - 6 Configuration

376 ConfigurationPerforming fine adjustment1) Determine the lower value (as low and constant as possible) with the reference measuring device. Example

Page 32

6 Configuration386.3 Digital inputIn addition to the analog inputs the module provides a digital input.The status of the digital input is indicated by

Page 33

396 ConfigurationSignal suppressionWhen signal suppression is active, the input signal and the inverting and delay parameters are irrelevant. In this

Page 34

Contents44.4 Functional test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 35

6 Configuration406.4 NV connecting listThe NV connecting list is used to link external inputs (NV_...) of the analog input module 8-channel to signals

Page 36

416 ConfigurationReplacement valueThe replacement value is used if the relevant signal is not available (connection to base unit interrupted or system

Page 37

6 Configuration426.4.1 Digital signals (overview)The following table contains all signals that are available in the NV connecting list for connec-tion

Page 38

436 ConfigurationAlarm analog variablesAlarm1 ExAI1 to Alarm1 ExAI64 Alarm signal 1 of analog variable 1 to 64Alarm2 ExAI1 to Alarm2ExAI64 Alarm signa

Page 39

6 Configuration44Alarms/ FaultsCAlarm/Fault System collective alarm or system fault (cen-tral processing unit and modules)CAlarm/Fault ackn. System co

Page 40

456 ConfigurationMultichannel controller moduleController C01ManualMode to C04ManualModeManual mode active for controller channel 1 to 4C01TuneActive

Page 41

6 Configuration46Analog input module 4-channelAnalog inputs AI01Alarm1 to AI04Alarm1 Alarm signal 1 of analog input 1 to 4AI01Alarm2 to AI04Alarm2 Ala

Page 42

476 Configuration6.4.2 Replacement values (overview)The following table contains the replacement values with their factory settings. Replacement value

Page 43

6 Configuration48

Page 44

497 Online parameters7.1 Calibrate / test7.1.1 Analog inputSetup dialogParameterTIP!An active connection between the setup program and the central pro

Page 45

51 Introduction1.1 Available technical documentationThe documents specified below are available for the measuring, control, and automation sys-tem.1.1

Page 46

7 Online parameters50TestThe results of the test measurement are shown in the display field.7.1.2 Digital inputSetup dialogParameterParameter Selectio

Page 47

517 Online parameters7.1.3 LED testSetup dialogParameterParameter Selection/settings DescriptionS LED To test the LED, click the required status to se

Page 48

7 Online parameters527.1.4 Calibration constantsSetup dialogThis dialog displays the calibration constants of the analog inputs.7.1.5 VersionsSetup di

Page 49 - 7 Online parameters

538 Appendix8.1 Technical data8.1.1 Analog inputsGeneral informationRTD temperature probeMeasuring circuit monitoringIn the event of an error the digi

Page 50

8 Appendix548.1.3 Electrical data8.1.4 Case and ambient conditions8.1.5 Approval/approval marksVoltage supplyConnection Lateral (feed via base unit or

Page 52

JUMO GmbH & Co. KGStreet address:Moritz-Juchheim-Straße 136039 Fulda, GermanyDelivery address:Mackenrodtstraße 1436039 Fulda, GermanyPostal addres

Page 53 - 8 Appendix

1 Introduction61.1.4 Special modules1.1.5 Operating, visualization, recording1.1.6 Power supply unitsProduct Type of documentation No. Printed PDF fil

Page 54

71 Introduction1.2 Safety information1.2.1 Warning symbols1.2.2 Note signsDANGER!This symbol indicates that injury to persons caused by electrical sho

Page 55

1 Introduction81.2.3 Intended useThe modules described are intended for measuring, control, and automation tasks in an indus-trial environment, as des

Page 56

91 Introduction1.3 Acceptance of goods, storage, and transport1.3.1 Checking the delivery• Ensure that the packaging and contents are not damaged • Ch

Comments to this Manuals

No comments